PROFIBUS Cable 2xAWG24 – Braid shielded - PUR jacket AWM
Style 20233 (80°C / 300V)
CODE: 86A24SS203-E30
Homologation UL AWM style: 20233
Accordance to Directives:2014/35/UE; 2011/65/CE; 2015/863/UE
Accordance to Directives:
Electrical Equipment (Safety) Regulations 2016
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012.
GENERAL CONSTRUCTION
Conductor
Stranded bare copper wire 0.13mm; Nom. 0.25mm² - AWG24; nominal diameter 0.65mm.
Lay agree with UL 758 tab 5.9; conform to EN 13602 - ETP1, DIN 40500 E-Cu 58.
Insulation
Foam polyolefin; Nominal diameter 2.55mm; Colour cores: Green – Red..
Assembly
Two cores stranded together with filler in gap.
Shield
- Al/PET tape; Aluminium face outside; optical coverage 100%.
- Braid type; tin copper wire; nominal optical coverage 85%.
Protective tape
Taper over assembly and over shield.
Jacket
PUR (ether base), hardness 90 ShA; Diameter 8.1 ±0.2mm; colour Violet similar RAL4001; conform to UL AWM Style 20233.
TECHNICAL DATA
Electric
Operating voltage 300 Vrms
Voltage test 700 Vac
Max conductor resistance 78.4 Ω/Km (IEC60344)
Nominal impedance @ 1MHz 150 Ω
Nominal capacitance @ 1KHz: 29 pF/m
Physical
Operating temperature range -40°C to +80°C (fixed)
Operating temperature range -25°C to +80°C (flex, free movement not continuous)
Minimum bending radius 7.5 x D (fixed)
Minimum bending radius 12.5 x D (flex, free movement not continuous)
Chemical
Oil resistant yes (UL 758)
Silicone, Pb, Cd, Hg, FCKW free yes
Halogen free yes (CEI EN 60754-1 / VDE 0482-754-1)
Electrical and transmission
properties at 20°C
Nominal impedance @ 1MHz 150 Ω
Nominal capacitance @ 1KHz 29 pF/m
Propagation velocity approx 67%
Insulation reistance >5.0 GxKm
Attenuation at 250 KHz <0.9 db/100m
Attenuation at 625 KHz <1.0 db/100m
Attenuation at 1.25 MHz <1.4 db/100m
Attenuation at 4 MHz <2.7 db/100m
Attenuation at 16 MHz <5.5 db/100m
Flame
Flame resistant UL Cable flame test; CSA FT1; IEC 60332-1-2
Movement data @20°C
Minimum bending radius 20 x D
Bending cycles 500000 cycles (1 Mio stroke)
Max speed 120 m/min
Max acceleration 60 m/sec²
BUS and DATA cables this type of cable is used to manage data transmission for complex systems where impedance values and transmission speed are required. Two product ranges are available for dynamic installation or static installation, compliant with UL, CSA and DESINA approvals.