• November 25, 2024
  • Via Mappano 30/G-H 10071 Borgaro Torinese

PROFIBUS

PROFIBUS Cable 2xAWG24 – Braid shielded - PUR jacket AWM
Style 20233 (80°C / 300V)

CODE: 86A24SS203-E30

Homologation UL AWM style: 20233

Accordance to Directives:2014/35/UE; 2011/65/CE; 2015/863/UE

Accordance to Directives:

Electrical Equipment (Safety) Regulations 2016

The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012.

GENERAL CONSTRUCTION

Conductor

Stranded bare copper wire 0.13mm; Nom. 0.25mm² - AWG24; nominal diameter 0.65mm.
Lay agree with UL 758 tab 5.9; conform to EN 13602 - ETP1, DIN 40500 E-Cu 58.

Insulation

Foam polyolefin; Nominal diameter 2.55mm; Colour cores: Green – Red..

Assembly

Two cores stranded together with filler in gap.

Shield

- Al/PET tape; Aluminium face outside; optical coverage 100%.
- Braid type; tin copper wire; nominal optical coverage 85%.

Protective tape

Taper over assembly and over shield.

Jacket

PUR (ether base), hardness 90 ShA; Diameter 8.1 ±0.2mm; colour Violet similar RAL4001; conform to UL AWM Style 20233.

TECHNICAL DATA

Electric

Operating voltage 300 Vrms
Voltage test 700 Vac
Max conductor resistance 78.4 Ω/Km (IEC60344)
Nominal impedance @ 1MHz 150 Ω
Nominal capacitance @ 1KHz: 29 pF/m

Physical

Operating temperature range -40°C to +80°C (fixed)
Operating temperature range -25°C to +80°C (flex, free movement not continuous)
Minimum bending radius 7.5 x D (fixed)
Minimum bending radius 12.5 x D (flex, free movement not continuous)

Chemical

Oil resistant yes (UL 758)
Silicone, Pb, Cd, Hg, FCKW free yes
Halogen free yes (CEI EN 60754-1 / VDE 0482-754-1)

Electrical and transmission
properties at 20°C

Nominal impedance @ 1MHz 150 Ω
Nominal capacitance @ 1KHz 29 pF/m
Propagation velocity approx 67%
Insulation reistance >5.0 GxKm
Attenuation at 250 KHz <0.9 db/100m
Attenuation at 625 KHz <1.0 db/100m
Attenuation at 1.25 MHz <1.4 db/100m
Attenuation at 4 MHz <2.7 db/100m
Attenuation at 16 MHz <5.5 db/100m

Flame

Flame resistant UL Cable flame test; CSA FT1; IEC 60332-1-2

Movement data @20°C

Minimum bending radius 20 x D
Bending cycles 500000 cycles (1 Mio stroke)
Max speed 120 m/min
Max acceleration 60 m/sec²

BUS and DATA cables this type of cable is used to manage data transmission for complex systems where impedance values and transmission speed are required. Two product ranges are available for dynamic installation or static installation, compliant with UL, CSA and DESINA approvals.

Do you want to receive the technical specifications?

Fill out the form below

Contact Form inglese specifiche tecniche